MANUAL
GB CHATTER NOTIFICATION CONFIGURATION 1303
17
Data will be treated by the STORMFLOW plug-in
Second element - input type
for this rule:
Data must come from a digital input
Data must come from a analog input
Data must come from a counter on a digital input
Data must come from a Modbus input
Data must come from an internal measurement
Third element - input number
data for this rule:
Data must come from X-input number 1
Data must come from X-input number 2
Data must come from X-input number 3
Data must come from X-input number 4
Fourth element - data output
The fourth element is a number designating which data, this rule will output to a recipient, typically a SCADA-system.
Data output is divided into three different groups;
marked with a Chatter in the table below.
Database in the table below.
Output of data from the STORMFLOW plug-in, marked with an Stormflow in the table below.
measurement or alarm which is processed by this rule.
Output the battery voltage in mV from the internal battery in the current MJK
Output the GSM signal strength as a value between 1 and 31 as recorded for
The signal strength is marginal
The signal strength is is acceptable
The signal strength is is good
The signal strength is is excellent
reset to the file with comma-separated values.