Strona 1 - Maintenance Manual

AquaForce Variable Speed PackageSystemMechanicalInstallation,Operation, andMaintenance Manual

Strona 2

Transportation and StorageInspect the deliveryInspect the package1. Inspect the package for damaged or missing items upon delivery.2. Note any damaged

Strona 3 - Table of Contents

Storage between useObserve the following for long-term storage of a pump station.• Insure system is drained of any water.• Remove transducers to ensur

Strona 4

Product DescriptionGeneral descriptionDescriptionA pump station is a pre-engineered and fabricated line of packaged booster systems thatprovides:• Ene

Strona 5 - Introduction and Safety

• Serial number• Item numbers of the required parts.Date CodePump BoostDischarge PressureSuction PressureStation FlowLargest Motor HPSCCRSystem FLASta

Strona 6 - Environmental safety

InstallationField connectionsDiagramsActual equipment manufacturers/models installed are system specific. Refer to specificmanufacturer Installation, Op

Strona 7 - User safety

Guideline Explanation/commentMake sure that the space around the pump package issufficient.This facilitates ventilation, inspection, maintenance, andse

Strona 8 - Product warranty

Grout the baseplateRequired equipment:• Cleaners: Do not use an oil-based cleaner because the grout will not bond to it. Seethe instructions provided

Strona 9 - Warranty claim

Commissioning, Startup, Operation,and ShutdownPreparation for startupDANGER:Electrical hazard sufficient to kill. Always disconnect and lock out the po

Strona 10 - Transportation and Storage

Checks CheckedCheck that the drain plugs are installed before filling system. Inspect all piping joints for tightness.Joints can become loose during tr

Strona 11

Pump station startupConfirm the job site voltage1. Check these items before you apply power or close the disconnect:a) Check all of the power wiring co

Strona 13

Start the package1. Close the disconnect in order to apply power to the package.2. Turn the panel switch to the local position.3. Watch the screen as

Strona 14

MaintenancePrecautionsDANGER:Electrical hazard sufficient to kill. Always disconnect and lock out the power before youservice the unit.WARNING:• This m

Strona 15 - Foundation requirements

Motor lubrication checks• For grease-filled bearings, make sure that grease is not all over the inside of the motorand in the bottom of the motor. This

Strona 16 - Piping checklist

TroubleshootingPump station troubleshootingDANGER:• Personal injury hazard. Troubleshooting a live control panel exposes personnel tohazardous voltage

Strona 17 - Preparation for startup

Cause RemedyThe fuses are blown or breakers are tripped. Check circuit breaker and fuses.Transducer isolation valves are closed. Make sure that the tr

Strona 18 - Final adjustments

The pump station experiences excessive vibrationCause RemedyThe motor, pump, or piping is loose. Make sure that all fasteners and components areproper

Strona 19 - Pump station startup

Cause RemedyThe diaphragm tank is faulty. Check for a properly installed diaphragm tank. Has thetank failed? Has the tank been charged to the properop

Strona 20 - Test the package

Technical ReferencePump station numbering systemThe pump station label located on the inside of the control enclosure door identifies theproduct code n

Strona 21 - Maintenance

Seventh character: Stages / impeller size1 = 1, 2 = 2, 3 = 3, and so forthEighth character: reduced number of stages0 = 0 reduced, 1 = 1 reduced, 2 =

Strona 22

Fifth character: Supply voltage2 = 208 V / 1 PH / 60 Hz 6 = 460 V / 3 PH / 60 Hz3 = 230 V / 1 PH / 60 Hz 7 = 575 V / 3 PH / 60 Hz4 = 208 V / 3 PH / 60

Strona 23 - Troubleshooting

Table of ContentsIntroduction and Safety...

Strona 24

Pump station with SSH pumpsExample product codeV 2 HE F 4 P A L 2 BCDNumbering system definitionsFirst character: Variable or constant speedV = variabl

Strona 25

Seventh character: TrimF — — — 4-11/166-1/8 4-13/166-3/16 6-1/16 7-1/2 7-1/2 8-1/4 7-15/16 — —G — — — 4-3/8 — 4-7/16 — 5-5/8 7-1/8 7-1/8 — 7-11/16 — —

Strona 28 - Pump station with NPE pumps

Xylem |’zīləm|1) The tissue in plants that brings water upward from the roots2) A leading global water technology companyWe're 12,500 people unifi

Strona 29

Monthly maintenance...19Troublesho

Strona 30 - Pump station with SSH pumps

Introduction and SafetyIntroductionPurpose of this manualThe purpose of this manual is to provide necessary information for:• Installation• Operation•

Strona 31

Hazard levelsHazard level IndicationDANGER: A hazardous situation which, if not avoided, will result indeath or serious injuryWARNING: A hazardous s

Strona 32

WARNING:Radiation Hazard. Do NOT send the product to Xylem if it has been exposed to any nuclearradiation.Electrical installationFor electrical instal

Strona 33

• Rinse the components in water after you disassemble the pump.• Do not exceed the maximum working pressure of the pump.• Do not open any vent or drai

Strona 34 - Xylem

Warranty claimXylem products are high-quality products with expected reliable operation and long life.However, should the need arise for a warranty cl